Cummins KTA50 Series Diesel Generator Sets

Overview

This Cummins Power Generation commercial generator set is a fully integrated power generation system, providing optimum performance, reliability, and versatility for stationary standby, prime power, and continuous duty applications.

  • Cummins® heavy-duty engine – Rugged 4- cycle industrial diesel delivers reliable power, low emissions and fast response to load changes.
  • Permanent magnet generator (PMG) – Offers enhanced motor starting and fault clearing short circuit capability.
  • Alternator – Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings; low waveform distortion with non-linear loads, fault clearing short-circuits capability, and class F or H insulation.
  • Control system – Standard PowerCommand® electronic control provides total system integration including remote start/stop, precise frequency and voltage regulation, alarm and status message display, AmpSentry protection, output metering, auto-shutdown.
  • Cooling system – Standard integral set mounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.
  • Enclosures – Optional weather-protective and sound-attenuated enclosures are available.
  • Warranty and service – Backed by a comprehensive warranty and worldwide distributor network.

Explore list of Cummins Generators before you buy any other generator set.

Specifications

Governor regulation class ISO 8528 compliant Voltage regulation, no load to full load ± 1% Random voltage variation ± 1% Frequency regulation Isochronous Random frequency variation ± 0.25% EMC compatibility BS EN 61000-6-4 / BS EN 61000-6-2.
Design 4 cycle, V-black, turbo charged and after-cooled Bore 158.8 mm (6.25 in) Stroke 158.8 mm (6.25 in) Displacement 50 L (3067 in 3 ) Cylinder block engine Sixteen-cylinder vee formation, direct injection, four-cycle diesel Battery capacity 1800 amps at ambient temperature 32ºF (0°C) Battery charging alternator 55 amps Starting voltage 24- volt, negative ground Fuel system Direct injection Fuel filter Dual spin on paper element fuel filters with standard water separator Air cleaner type Dry replaceable element Lube oil filter type(s) Spin-on paper element full flow and bypass lube oil filters Standard cooling system 104ºF (40ºC) ambient radiator.
Design Brushless, 4 pole, drip proof revolving field Stator 2/3 pitch Rotor Direct coupled by flexible disc Insulation system Class H Standard temperature rise Exciter type PMG (Permanent magnet generator) Phase rotation A (U), B (V), C (W) Alternator cooling Direct drive centrifugal blower fan AC waveform total harmonic distortion No load <1.5%. Non distorting balanced linear load <5% Telephone influence factor (TIF) < 50% per NEMA MG1-22.43 Telephone harmonic factor (THF) No load <1.5%. Non distorting balanced linear load <5%.

Models available in Cummins KTA50 Series:

Generator Model Frequency Standby Rating (kW / kVA) Prime (kW / kVa) Spec Sheet
C1250D2R 50 1120 / 1400 1006 / 1258 EMERS-5884-EN
C1400 D5 50 1120 / 1400 1000 / 1250 SS16-CPGK
C1400 D5 50 1120 / 1400 1000 / 1250 SS16-CPGK
C1250D2R 60 1270 / 1588 1120 / 1400 EMERS-5884-EN
C1250 D6 60 1270 / 1588 1120 / 1400 SS16-CPGK
C1675 D5 50 1340 / 1675 1120 / 1400 SS16-CPGK
C1675 D5 50 1340 / 1675 1120 / 1400 SS16-CPGK
C1675 D5A 50 1340 / 1675 1200 / 1500 SS16-CPGK
C1675 D5A 50 1340 / 1675 1200 / 1500 SS16-CPGK
C1500 D6 60 1545 / 1931 1286 / 1608 SS16-CPGK